WhatsApp

Article

FISH ON PURE O₂? THE CO₂ PROBLEM TOWERS ARE BUILT TO SOLVE

Industry: Aquaculture | Process: Recirculating_Aquaculture_Systems_(RAS)

In RAS, fish and microbes respire oxygen and produce CO₂, which must be stripped to avoid blood pH shifts that can halve hemoglobin–oxygen (Hb–O₂) affinity and trigger pathologies such as nephrocalcinosis (learn.farmhub.ag). Unlike aeration with ambient air, systems that inject pure O₂—such as low‑head oxygenators (LHOs)—lose most gas‑exchange area and do not purge CO₂; without a dedicated stripper, CO₂ accumulates to toxic levels (researchgate.net) (learn.farmhub.ag). Industry practice is to pair high‑oxygen systems with a comparable CO₂‑removal unit (studylib.net).

Packed‑column stripping towers (counter‑current)

These vertical towers are filled with plastic media; water trickles down while air is forced up in counter‑current flow. The design increases surface area and contact time, driving degassing (researchgate.net) (learn.farmhub.ag).

In lab tests by Hu et al. (2011), single‑pass CO₂ removal reached 80–92% when the air‑to‑water volumetric ratio (gas‑to‑liquid ratio, GLR) was ~5–8; removal asymptoted at about 6.4 mg CO₂/L (≈6.4 g/m³) at high GLR (researchgate.net) (c.coek.info) (c.coek.info). The data fit an exponential model: “CO₂_removed (mg/L) ≈ 6.44 – 5.82·(0.648^GLR)” (r²=0.91), so GLR≈5 reached ≈6.0 mg/L removal (≈85% of the ~7.0 mg/L inlet) and GLR≈8 gave ≈6.4 mg/L (≈90–92% removal) (c.coek.info) (c.coek.info), with minimal gains beyond GLR≈8 (researchgate.net). At typical design conditions (20 °C, fresh water), Henry’s law (H≈1.1) predicts GLR≈5–10 for 80–95% removal, aligning with these results (researchgate.net) (lenntech.com).

c.coek.info researchgate.net Figure: CO₂ removal by packed‑column degasser vs. air:water (G/L) ratio (from Karimi et al., 2020). High GLR yields diminishing improvement.

Field results and tower dimensions

Full-scale systems rarely match lab ideals. In a salmon farm, two 1‑m towers packed with 4–5 cm plastic achieved only ~36% single‑pass removal at GLR ~9.7, and ~33% at GLR ~5.3 (researchgate.net). Field factors cut efficiency: shorter contact time, biofouling, uneven flow. In practice, 40–70% removal per pass is usually cited (researchgate.net).

Towers are usually tall (1–3 m) with open media. Colt & Bouck (1984) recommend ~1–3 m to achieve a ΔP ~20 mmHg CO₂ driving force and ≥90% O₂ saturation. Packing size trades height versus air pressure drop. In oxygen-saturated water (high dissolved oxygen), a vacuum column can shorten the needed height (researchgate.net).

The overall transfer rate (K_La, an overall mass-transfer coefficient times area) for CO₂ in towers can be on the order of 1–2 h⁻¹ in practice. Eshchar et al. measured K_La ≈1.5 h⁻¹ for a paddlewheel (air-driven) and 0.76 h⁻¹ for a diffused-air aerator. These gave 1.2 and 0.9 kg CO₂/kWh, respectively. That implies ~0.8–1.2 kW per kg/h of CO₂ removed. Packed-tower energy use is similar (researchgate.net) (researchgate.net).

Cascade and spray towers (ventilated)

Open-aeration devices, such as waterfalls over baffles or stacked blocks, work like packed towers but use simpler media. Summerfelt’s 2003 study tested “forced-ventilated cascade” towers 0.9–1 m tall. Single-pass removal was ~22% at GLR ~2.5, ~33% at GLR≈5.3, and ~36% at GLR≈9.7. Each 1 m pass removed only ~0.5–6 mg/L depending on GLR. Therefore multiple stages or very high airflow are needed for >80% removal (researchgate.net). Cascade units usually plug with solids less than fine-packed columns. Plugging and bed fouling are recurring concerns. Separate solids removal units, such as a manual screen (removes debris >1 mm), are outside the scope of the cited tests.

Oxygenators: O₂ in, CO₂ stuck

LHOs (stacked plate or spiral contactors) are built to inject pure O₂, with high oxygen‑transfer efficiency (reported up to ~2 kg O₂/kWh and, with head, up to 80 kg O₂/kWh), but have very limited CO₂‑stripping capability. With only an LHO and a closed headspace, CO₂ accumulates because no external low‑CO₂ air is contacted with the water (researchgate.net) (researchgate.net) (learn.farmhub.ag). They are always used alongside a venting step; for example, Glaciersprings Trout Farm (Canada) ran cascade columns ahead of an LHO to strip CO₂ before final O₂ saturation (researchgate.net). The prudent assumption is ~0–10% CO₂ removal per pass from the LHO itself—essentially zero without venting (learn.farmhub.ag) (studylib.net).

Other aerators—venturi injectors, paddlewheels, diffusers—strip CO₂ by creating surface area but are less controllable than towers. A paddlewheel (blown air) reached K_La≈1.55 h⁻¹ with ~1.2 kg CO₂/kWh; a diffused‑air aerator delivered K_La≈0.76 h⁻¹ and ~0.9 kg/kWh (researchgate.net) (researchgate.net). Only dedicated degassing towers ensure controlled CO₂ removal (learn.farmhub.ag) (studylib.net).

Comparative effectiveness and energy

Packed tower (1–3 m tall): >80% removal achievable in lab at GLR≈5–8 (80–92%); field columns often see 30–60% per pass. K_La on the order of 1–2 h⁻¹ (CO₂) depending on height and media; energy roughly ~1 kg CO₂ removed per kWh (researchgate.net) (c.coek.info) (studylib.net).

Cascade (0.5–1 m per stage): ~20–40% removal per stage at GLR=3–6; K_La typically ≤1 h⁻¹ (researchgate.net).

Low‑Head Oxygenator: ~0–10% CO₂ removal per pass (essentially none without venting). High O₂ transfer (2–80 kg O₂/kWh with head), but CO₂ must be stripped separately (learn.farmhub.ag) (studylib.net) (researchgate.net).

Other aerators (paddle, diffusers): limited by surface. Diffused-air K_La≈0.76 h⁻¹ and ~0.9 kg CO₂/kWh. Paddlewheel K_La≈1.55 h⁻¹ and ~1.2 kg/kWh (researchgate.net) (researchgate.net).

Design targets and CO₂ thresholds

Design targets follow fish tolerance. Blood-acid organoleptic studies suggest keeping CO₂ below ~5–10 mg/L (CO₂ partial pressure <3 mmHg) in trout/salmon. Some species tolerate more. RAS usually run at ≤10–15 mg/L CO₂ in tank effluent (learn.farmhub.ag).

Step‑by‑step sizing guide (by load and flow)

ChatGPT Image Feb 27, 2026, 08_50_43 AM

  1. Estimate the CO₂ load. Fish produce about 0.6–0.7 kg of CO₂ per kg of feed consumed. If you feed at F (kg/day), CO₂ ≈ 0.66·F (kg/day). For example, 100 kg feed/day gives about 66 kg CO₂/day (≈2.75 kg/h). You can also base it on O₂ demand. For salmonids, assume about 20 g O₂/kg·h at about 15–20 °C. With a respiratory quotient RQ≈0.9, CO₂ output is about 18 g/(kg·h). Therefore 1,000 kg of fish consume about 20 kg O₂/h and produce about 18 kg CO₂/h (researchgate.net).

  2. Determine the water flow through the degasser. Let the recirculating flow Q (m³/h) cycle the tank several times per hour. The needed per-pass drop is ΔC (mg/L) = CO₂ production [mg/h] / Q [L/h]. For example, 2.75 kg/h production (2,750,000 mg/h) at Q=400 m³/h (400,000 L/h) needs ΔC≈6.9 mg/L. The stripper must reduce CO₂ by that amount (for example, from about 8 mg/L to about 1 mg/L).

  3. Choose GLR (air:water ratio). GLR≈5–8 achieves ~80–90% removal of that ΔC in one pass. Treating 400 m³/h implies air ≈ 2,000–3,200 m³/h (≈0.6–0.9 m³/s). Lower GLR can work with multi‑pass; higher GLR asymptotically approaches 90–95% removal but at higher energy cost. Diminishing returns set in beyond GLR≈8 (researchgate.net) (c.coek.info).

  4. Column dimensions. Set the superficial water velocity and the packing height for the needed ΔC. For 80–90% removal, a packed height of 2 m or more is common. The cross-section follows from Q and the allowable velocity. For example, 400 m³/h over 2 m² gives about 0.055 m/s. A 3 m height is a typical starting point. Colt & Bouck suggest 1–3 m for ΔP≈20 mmHg CO₂. Media with large voids reduce clogging but need more height. In oxygen-saturated water, a vacuum column can shorten the height (researchgate.net).

  5. Validate K_La / removal. Use C_out = C_in·exp(–K_La·t) with t = H/V (height/velocity). For H=3 m and Q=400 m³/h over A=4 m², V≈0.028 m/s, so t≈107 s. With K_La=1 h⁻¹ (=0.000278 s⁻¹), exp(–K_La·t) ≈ 0.97. That is far too small a reduction. Therefore the effective K_La in packed media must be much higher. Vendor or empirical data are usually used to refine t and A.

  6. Energy and air. A rule of thumb is about 1 kWh of blower per 1–1.2 kg CO₂ removed. In the example, 66 kg/day (2.75 kg/h) is removed at about 1.2 kg/kWh. Therefore the blower needs about 2.3 kW (researchgate.net).

  7. Field margins and fouling. Actual efficiency is usually lower, for example because of rapid loading, biosolids or temperature. Therefore design conservatively. Studies note about 40–50% per pass in practice. You may need multiple towers or a higher GLR. Plan for bed fouling so the bed can be cleaned. (researchgate.net). Separate filtration steps are different unit operations and the cited degassing tests do not cover them. One example is a cartridge filter, which removes 1–100 micron particles.

Rule‑of‑thumb capacity matching

A practical rule is to match degasser capacity to oxygenation capacity: a system delivering O₂ at rate X should strip the CO₂ load corresponding to that oxygen delivery (studylib.net). Numerically: CO₂ to remove (g/h) = (fish biomass kg) × (gO₂/kg·h) × RQ ≈ (kg feed/day × 0.66 / 24) × 1000. Given water flow Q (m³/h), ΔC = (g/h CO₂)/(1000·Q). Choose GLR≈5–8 to achieve that ΔC, then set column area based on practical velocities (~0.02–0.1 m/s) and ~2–3 m height. Each RAS is unique, so empirical adjustment is typical; beyond GLR 8–10, additional CO₂ stripping is minimal (researchgate.net) (c.coek.info). Designers aim to hold tank CO₂ at safe levels (e.g., <10–15 mg/L) by matching degasser throughput to fish load (researchgate.net) (studylib.net).

Sources: Peer‑reviewed RAS engineering studies and reviews (researchgate.net) (researchgate.net) (researchgate.net) (studylib.net), plus technical analyses (learn.farmhub.ag) (researchgate.net). All performance figures and calculations above are drawn from these references.