Cooling Towers as a Water-Saving Arena: Drift Eliminators and High Cycles Make a Big Difference

In refineries, cooling towers can “drink” almost all the incoming water. Data shows that simple measures—maximizing cycles of concentration and installing high-efficiency drift eliminators—change the water-saving game, even opening the door to process-water reuse such as stripped sour water.

In many industrial facilities, up to 95% of the incoming raw water circulates through cooling towers—a figure that makes this equipment a primary conservation target. In water-stressed regions such as Indonesia, rising costs and regulations are pushing refineries to cut their dependence on fresh water. The EPA's WaterSense guidance notes: raising cycles from 3 to 6 alone cuts makeup water by about 20% (EPA WaterSense).

The scale of this implementation is real. One study found that raising cycles from 6.5 to 9 would save more than 1.1×10^6 m³/year for the same cooling load (study of cycles of concentration and corrosion). Meanwhile, a simple upgrade to high-performance drift eliminators reduces “entrained droplets” (drift) to near-zero levels—cutting wasted water and treatment chemicals carried along.

Cooling tower water loss profile

The main water losses in cooling towers come from evaporation (about 1% of the flow for every 5.6 °C temperature drop), bleed/blowdown (discharging some water to control total dissolved solids/TDS), and, in smaller proportions, leaks and drift (droplets carried away by exhaust air). Without an eliminator, drift can be 0.05–0.2% of the circulating flow (EPA).

Because blowdown increases as TDS rises, conservation strategies focus on two levers: reducing drift and maximizing cycles of concentration (COC; the ratio of dissolved salt concentration in the tower circulation to that in the makeup water).

High-efficiency drift eliminators

A drift eliminator captures droplets entrained in the air stream and returns them to the collection basin. High-performance designs can cut drift to ≪0.005% of the circulation flow (EPA). In practice, installing modern models often reduces drift by >90–99%: on a 200 m³/h tower, an old eliminator (0.002% drift) loses ~4 L/h, while a high-eff model (0.0005% drift) loses only ~1 L/h, a difference that accumulates to about 26 m³/year per tower (Vistech Cooling).

Important knock-on effects: less water and treatment chemical loss, a smaller environmental footprint from released tower water, and emissions compliance, because regulators (as well as Legionella safety guidelines) limit drift. A good tower chemical program, for example a cooling tower chemicals package, is a natural companion to this mechanical upgrade (EPA; Vistech Cooling).

Operation at the highest cycles of concentration

The higher the COC, the lower the blowdown, which directly reduces makeup water consumption. EPA calculates savings of ~17–20% when cycles are doubled: 3→6 cuts makeup by about 20% (EPA WaterSense). Tower water balance arithmetic (makeup = evaporation × COC/(COC − 1)) shows that raising COC from 2.2 to 10 lowers makeup by about 39% at the same cooling load.

With the right treatment, COC >10 is not utopian: the key is tight scaling control, because calcium and other ions precipitate when concentrated. Deposit inhibitors and pH control, for example through scale inhibitors, as well as softening based on an ion exchange softener, often come as a package, and carbon steel corrosion is kept at a low rate.

Field example: raising COC from 6.5 to 9 (saving >1.1×10^6 m³/year) succeeded only after pH was lowered and a Zn/Mercaptobenzothiazole inhibitor was added to prevent calcium orthophosphate precipitation (study of concentration cycles and corrosion). In practice, stepwise monitoring of hardness, Langelier Saturation Index/LSI (an indicator of calcium carbonate scaling tendency), and online meters—for example Betaqua Sentinel CTS—are highly recommended. With the right chemistry, COC can often be doubled or more above baseline, and a 20–40% reduction in blowdown can mean thousands of cubic meters of water saved per year for a large refinery. Precise dosing helps maintain the set point—for example, using a dosing pump for acid/alkali or inhibitor.

Corrosion correlation must be maintained as COC increases. A corrosion inhibitors program compatible with the tower chemistry acts as a safety fence when salt concentration rises (EPA WaterSense).

Alternative water sources as makeup

To further reduce raw water use, refineries can use non‑potable sources as makeup: treated effluent (industrial/municipal), rainwater, condensate, and internal streams. Many “reclaimed water” sources such as municipal secondary effluent carry high hardness, alkalinity, phosphate, ammonia, or organics—increasing the risk of scaling/corrosion (www.powermag.com). However, advanced treatment or a chemical program can address this.

A power plant study showed that municipal effluent with high phosphate (13 ppm PO₄) can still be run at high cycles with the addition of a “terpolymer” inhibitor, so expensive softening or polishing is not needed (www.powermag.com). If a physical‑chemical route is chosen, side‑stream options such as reverse osmosis (RO) are also commonly used to reduce the salt load.

Cooling tower blowdown recycling

Cooling tower blowdown can itself be recycled. A pilot test showed that blowdown reuse lowers the freshwater footprint by about 13% (www.sciencedirect.com). A case at a 750 MW power plant in Chile achieved 96% blowdown recovery by combining RO and a salt precipitation reactor—compared with ~55–60% for conventional RO (www.watertechonline.com). That means only 4% of the makeup needs fresh water—drastically cutting total use. When blowdown is recycled into makeup, cycles can be pushed to the chemical limit (because discharge limits are no longer a factor) (www.watertechonline.com; www.sciencedirect.com).

High-recovery RO operation requires tight scale control. Packages of membrane antiscalants are commonly used to maintain performance when salt concentration is high on the concentrate side.

Reuse of stripped sour water in refineries

Another internal opportunity is treated process water. At a refinery, sour water from crude distillation and hydrotreaters (water laden with H₂S/NH₃) is usually sent to a stripper to remove acid gas; the result is called stripped sour water (SSW). Instead of being discharged, SSW can be diverted to uses that do not require high quality. A study at Saudi Aramco's Ras Tanura refinery showed that SSW quality is adequate to replace boiler‑feed water in equipment “wash” duties (www.watertechonline.com).

Phased implementation (25%→50% replacement) has run stably and achieved ~33% SSW reuse, saving about US$1 million in the first year (www.watertechonline.com). Ras Tanura also plans to use the remaining SSW as cooling water (projected 50% reuse) once the supporting issues are addressed (www.watertechonline.com). Technically, this route requires characterization and simple pretreatment such as decantation, filtration, and ammonia control; for particulate polishing, sand silica media or a cartridge filter are often included in the filtration scheme.

Other non‑potable sources and disinfection

Other sources include rainwater, HVAC condensate, or industrial effluent; all require particulate removal and biocide addition (because even when “clean,” this water is not sterile). ASHRAE notes that air‑handler condensate—water that is essentially distilled—can meet ~10–40% of tower makeup demand in humid climates (ASHRAE Handbook). Rainwater harvesting yields ~1 L per mm of rain per m² of roof (ASHRAE Handbook). A biocides program is required to control microbial growth when these alternative sources are blended into the tower circuit.

Measured results and implementation practice

This strategy package delivers auditable results. DOE/EPA guidance projects a 20%–60% reduction in tower makeup water when COC is raised to the 6–10 range (EPA WaterSense), while reliable drift eliminators reduce drift to negligible levels (EPA). Industrial cases support this: the cited refinery successfully reuses ~33% SSW (with savings of ~US$1 million/year) (Ras Tanura refinery case study), and a power plant demonstration cuts blowdown discharge by ~91% (96% reuse) (750 MW plant case study).

On the execution side, best practices include measuring all water flows, real-time conductivity and pH control, and a consistently run tower chemical program. Blending or switching water sources must account for differences in chemistry (e.g. LSI, silica, chloride) so hidden corrosion does not occur. In the right configuration, the financial return—much less makeup water and lower operating costs—makes this step attractive. In many refineries, a scale inhibitor package, pH control, and membrane pretreatment such as membrane systems for reuse, backed by operational discipline, are enough to run aggressive COC without scaling. To design the package, see our cooling tower chemical program: scale and corrosion inhibitors, biocide, and dose monitoring to keep high COC safe.