Prevent Legionella in Industrial Cooling Towers

Prevent Legionella in Industrial Cooling Towers | Beta

Short answer: preventing Legionella in a cooling tower needs a water management programme that controls sediment/biofilm, temperature, water age, and disinfectant residual. Set control limits for the site, assign owners for monitoring and response, clean and disinfect on schedule, and escalate Legionella results together with operating trends. Do not judge from one test result alone.

Last technically reviewed: 17 July 2026.

Legionella can grow in warm water and spread through cooling-tower aerosols. This matters in Indonesia because cooling towers serve commercial buildings, hospitals, power generation, mining, petrochemical, pulp and paper, and other process plants. An effective programme protects workers, occupants, neighbouring communities, and operational continuity.

Illustration of Legionella bacteria

CDC guidance updated on 3 January 2025 groups the main factors under STAR: sediment and biofilm, temperature, water age, and disinfectant residual. CDC also notes that both open- and closed-circuit towers can release aerosols and need the same basic operation and maintenance protocols (CDC: Controlling Legionella in Cooling Towers).

Understanding Legionella Risk in Cooling Towers

The highest risk occurs when favourable growth conditions, aerosol exposure, and failed controls coincide. Map the water from make-up through basin, pump, heat exchanger/condenser, headers, active and standby cells, bypasses, side-stream filter, injection points, and blowdown. Include concealed low-flow pipework.

Risk pointWhy it mattersEvidence to inspectMain control
Basin and remote sumpSediment, warm water, and sludge support biofilmPhotographs, deposit inspection, temperature, cleaning historyCleaning, circulation, drainage, biocide programme
Fill pack, drift eliminator, nozzleLarge wet area; fouling disrupts distribution and can increase driftVisual inspection, pressure/flow distribution, eliminator conditionCleaning, component replacement, scale/corrosion control
Dead leg, bypass, standby cellWater age rises and disinfectant residual may disappearP&ID walkdown, valve position, flushing recordRemove dead legs where possible; scheduled flushing and circulation
Make-up and side-stream pointsIntroduce solids, nutrients, and organisms; filtration can failMake-up quality, filter differential pressure, turbidity/TSSPretreatment, filtration, maintenance
Aerosol zone and air intakeDrift may enter ventilation or expose workersSeparation/orientation, prevailing wind, eliminator conditionDrift elimination, placement, access control/PPE during work
Dosing and sensorsFeed loss or sensor drift removes a barrierTank level, pump calibration, residual trend, alarm historyAutomation, interlock, calibration, duty/standby

CDC describes 25–45°C as the most favourable Legionella growth range and recommends operating at the lowest practical water temperature. Temperature alone does not prove control. Biofilm, stagnation, sediment, and disinfectant residual must be evaluated together.

Best Practices for Legionella Prevention in Cooling Towers

An effective programme combines prevention, verification that tasks were completed, and validation that controls work. ANSI/ASHRAE Standard 188-2021 establishes minimum legionellosis risk-management requirements for building water systems, while ASHRAE Guideline 12 supports implementation (ASHRAE Standard 188-2021).

1. Risk Assessment

Team assessing Legionella risk

The water management team should map the system, potentially exposed populations, normal and standby conditions, seasonal changes, test history, and corrective actions. Include operations, maintenance, HSE, engineering, the facility owner, water-treatment service, and microbiology/laboratory competence.

Repeat the assessment after commissioning, retrofit, make-up-water or chemical changes, prolonged shutdown, worsening Legionella indicators, or a suspected illness. State who approves control limits and who can stop operation or order remediation.

2. Proper Design and Construction

Design should reduce stagnation, permit complete drainage and cleaning, provide safe access to basins/fill/nozzles, and use high-efficiency drift eliminators. CDC recommends avoiding dead legs, circulating water during intermittent operation, and installing an automated water-treatment system.

For new projects, review tower placement relative to air intakes, public areas, and work routes. For an existing tower, walk down the P&ID to find bypasses, equaliser lines, standby cells, remote sumps, and branches that lose circulation at partial load.

3. Comprehensive Maintenance Program

Maintenance should combine condition-based tasks with documented minimum intervals. CDC recommends offline disinfection and cleaning at least once a year. Do the work more often if the environmental load, deposits or performance indicators call for it. Follow-up must check that deposits are gone, the equipment works and chemical control is stable.

Use work orders for fill, nozzles, strainers, basin, drift eliminators, heat exchangers, side-stream filters, sensors, dosing pumps, valves, and standby components. If deposits cannot be controlled online, plan a cooling-tower cleaning service. The plan should cover isolation, waste handling, and post-work evidence.

4. Effective Water Treatment

Chemical treatment must control microbiology. However, it must also cover scale, corrosion, sediment, and material compatibility. Keep oxidising disinfectant measurable throughout each day, within the product label and programme limits. Dose non-oxidising products to the approved concentration and contact time.

Betagard Cooling Tower Chemicals cover biocides, inhibitors, dispersants, dosing, and monitoring. Product and dose selection must follow the water analysis, metallurgy, cycles of concentration, organic load, microbiology, the SDS/label, and discharge permits. Do not copy a setpoint from another tower.

5. Monitoring and Testing

Monitoring links a control limit to action. Increase the frequency when values become unstable, after an operating change, or during remediation. CDC does not specify one Legionella test schedule for every facility. The sampling plan should reflect its purpose, representative points, laboratory method, baseline, and population risk.

Parameter / evidenceControl limitInitial frequencyData ownerEscalation when out of limit
Disinfectant residualProduct- and site-specific rangeOnline/daily according to stabilityWater-treatment operatorVerify sensor and pump feed; correct per SOP; increase sampling
pH and conductivity/CoCProgramme and material limitsOnline/shift/dailyOperations/utilitiesInspect blowdown, make-up, dosing, and calibration
Temperature and stagnationAs low as practical; dead legs/standby per flush planDaily + weekly inspectionOperations/maintenanceRestore circulation, flush, review cell sequencing
Turbidity/TSS, sediment, biofilmBaseline/trend and inspection criteriaWeekly/monthly by riskWater treatment + maintenanceInspect basin/filter; clean or correct filtration
Legionella cultureWMP performance indicator; CDC: <10 CFU/mL indicates better control, ≥10 requires review/responseRisk-based sampling planHSE + competent laboratoryConfirm chain of custody; review WMP; correct and retest
Alarms, calibration, work ordersNo open critical alarm; calibration on timeWeekly/monthly reviewUtilities supervisorAssign owner and due date; assess interim operating risk

CDC values are performance indicators. They are not a “safe level” and not a prediction of illness. Read the results together with concentration, trend change, colonisation extent, species/serogroup, and facility conditions. CDC states that there is no known safe Legionella level (CDC: Routine Testing for Legionella).

Programme validation evidence matrix

Validation proves that the programme is controlling risk. It proves more than completed tasks. Use this matrix when the evidence for Legionella, biofilm, residual or physical condition starts to move away from baseline.

Validation evidenceSign that control is improvingIf it is not improving
Repeat Legionella results at the same pointTrend falls or remains below the WMP response limit after corrective actionCheck chain of custody, sample point, colonisation extent, species/serogroup, and remediation need
Disinfectant residual and pHResidual stays within the product range and pH supports its effectivenessCalibrate sensors, check water demand, tank level, dosing pump, and injection point
Biofilm/sediment inspectionBasin, fill, nozzles, and strainers remain clean after restartSchedule cooling-tower cleaning, side-stream filtration, or source-solids correction
Water balance and water ageStandby cells, bypasses, and dead legs have recorded flushing or circulationRevise cell operation, remove dead legs where practical, and audit valve position
Response recordsCorrective action closes with owner, date, photo/data, and approvalEscalate to HSE/engineering because the deviation has not been closed with evidence

6. Comprehensive Water System Management

Comprehensive cooling-tower water system management

At minimum, the programme should include a system diagram, team and responsibilities, hazard analysis, control limits, monitoring methods, corrective actions, verification, validation, communications, and record retention. Close each deviation with evidence. Do not close it with a note that it was “fixed”.

In Indonesia, Ministry of Health Regulation No. 2 of 2023 is the current general framework for environmental health and revoked Regulation No. 32 of 2017. For hospitals, Ministry of Health Regulation No. 7 of 2019 contains cooling-tower Legionella provisions. However, Regulation No. 2 of 2023 partially revoked its environmental-media standards. Each facility should confirm the current scope, permits and sector or local requirements with its HSE/legal function.

7. Use of Innovative Technology

Technology adds value when it closes a mapped risk. Automated monitoring of residual, pH, conductivity, flow and chemical level can shorten detection time. Betaqua Sentinel CTS supports those operating trends. Sensors still need correct sample locations, calibration, maintenance and an alarm response.

Side-stream filtration or make-up pretreatment such as ultrafiltration can reduce incoming solids and organisms. However, neither replaces the tower water management programme. UV also leaves no residual across the loop. Biofilm, dead legs and recontamination still need other controls.

8. Source Water Management

Make-up water determines the solids, nutrients, organisms and chemical demand that enter the tower. Monitor source changes, turbidity/TSS, hardness, alkalinity, chloride, silica, organics and relevant microbiology. Reuse water or condensate needs a separate hazard review before it is adopted as make-up.

Select pretreatment for the demonstrated problem: clarification/filtration for solids, softening or RO for selected minerals, and disinfection for the assessed risk. Do not increase cycles of concentration without calculating the effects on scale, corrosion, disinfectant residual and the blowdown permit.

9. Energy and Water Management

Water efficiency must not increase water age or reduce blowdown outside control limits. Optimise cycles of concentration while keeping chemistry, solids and microbiology within the approved range. Cell sequencing should balance energy savings with circulation through standby cells.

Trend make-up, blowdown, estimated evaporation, conductivity, heat load and fan/pump operation together. A water-balance anomaly may indicate leakage, valve error, excess drift or sensor failure. All of these affect operation and exposure risk.

10. Emergency Preparedness and Response

The response plan should distinguish a control deviation, a worsening routine test, suspected illness and an outbreak declared by public health. Define command, shutdown authority, area restriction, communication, sampling, contractor access, PPE/respiratory protection, waste handling and return-to-service criteria.

If you suspect illness or an outbreak, coordinate with public health before sampling and remediation. CDC recommends offline emergency cleaning and disinfection when the authority having jurisdiction suspects associated illness. Adapt the procedure to the materials, volume, configuration, chemical label, worker safety and discharge rules.

Cleaning and disinfection records to retain

  1. Tower/cell ID, date, reason for work, pre-shutdown operating condition, and person in charge.
  2. Photographs/findings for basin, fill, nozzles, drift eliminator, strainer, dead legs, and accessible heat exchangers.
  3. Chemical and batch/lot, target and actual concentration, pH, contact time, temperature, and test instrument.
  4. Isolation sequence, fan/pump status, area restriction, PPE, and disposal route.
  5. Rinse result, post-work inspection, sensor calibration, restart checklist, and new residual/chemistry baseline.
  6. Pre- and post-work Legionella results when needed, including method, location, time, laboratory, and chain of custody.
  7. Corrective action, owner, due date, verification, and return-to-service approval.

Conclusion

Legionella control is a repeating management system. It is not a one-off dose or cleaning visit. The risk map shows where growth and aerosol spread can occur. Control limits give signals. Action owners close deviations. Records show whether the programme was implemented.

PT Beta Pramesti Asia can support water-chemistry review, a cooling-tower biocide programme, monitoring and cleaning scope. Public-health decisions, clinical diagnosis and outbreak declarations remain with qualified health professionals and the relevant authority.

For chemicals, cleaning and programme support for Legionella control in Indonesia, see Legionella control for cooling towers from PT Beta Pramesti Asia.

Questions and Answers

Q1: Why are cooling towers in Indonesia at high risk of Legionella growth?

Cooling towers create aerosols. They contain wet surfaces, basins and circulation networks that may hold warm water, biofilm, sediment or stagnation. A tropical climate can extend warm conditions. However, the risk at each facility still depends on design, operation, make-up quality, maintenance and how well the water management programme works.

Q2: How can the use of technologies such as ultrafiltration help in the control of Legionella in cooling towers?

Ultrafiltration on make-up water can reduce incoming particles and microbial load when it is correctly designed and operated. It does not control growth in the basin, fill, dead legs or loop after recontamination. Therefore it must be combined with circulation, cleaning, corrosion/scale control, disinfectant residual and validation.

Q3: What is the role of automated monitoring in Legionella prevention in cooling towers?

Automated monitoring gives earlier warning when the disinfectant residual, pH, conductivity, flow or chemical level leaves its range. It does not measure the complete Legionella risk directly. Sensors need calibration, manual cross-checks and representative placement. An operator also needs to respond within a set time.

References

  1. CDC, Controlling Legionella in Cooling Towers, updated 3 January 2025.
  2. CDC, Routine Testing for Legionella, updated 3 January 2025.
  3. ANSI/ASHRAE Standard 188-2021, Legionellosis: Risk Management for Building Water Systems.
  4. Indonesia Ministry of Health Regulation No. 2 of 2023 implementing Government Regulation No. 66 of 2014 on Environmental Health.
  5. Indonesia Ministry of Health Regulation No. 7 of 2019 on Hospital Environmental Health, including the partial-revocation status recorded by BPK.